D. Definite time current function settings - Current-DT
Summary of parameters:
Text
Unit
ParSet 4..1
Trip
Delay
s
I-Setting
IN
MaxMin
NrOfPhases
CurrentInp
CT/VT-Addr
BlockInp
BinaryAddr F
Trip
SignalAddr ER
Start
SignalAddr ER
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the tripping channel activated by the tripping O/P of
the function (matrix tripping logic).
Delay
Time between the function picking up and tripping.
I-Setting
Pick-up current setting.
Forbidden settings:
· > 1.6 I
when supplied from metering cores
N
· < 0.2 I
when supplied from protection cores.
N
MaxMin
defines operation as overcurrent or undercurrent or with
inrush blocking. Settings:
· MIN (3ph):
· MIN (1ph):
3-60
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
01.00
0.02
02.00
0.02
MAX (1ph) (Select)
001
1
0
(see Section
5.11.).
Undercurrent.
Three-phase functions detect the highest
phase current.
Not permitted for single-phase functions.
Undercurrent.
Three-phase functions detect the lowest
phase current.
Max.
Step
60.00
0.01
20.00
0.01
3
2