ABB REG316 4 Series Operating Instructions Manual page 161

Numerical generator protection
Table of Contents

Advertisement

REG 316*4 1MRB520049-Uen / Rev. F
As can be seen from
protection of 95 % is 5 % of U
the generator stator winding, the cables to the step-up trans-
former and the delta-connected windings of the step-up trans-
former.
The capacitances between primary and secondary of the step-up
transformer conduct currents emanating from E/F's on the HV
side to the LV side and can cause false tripping of the stator E/F
protection. The capacitive coupling of E/F currents on the HV
side takes place regardless of whether the HV star-point is
grounded or not. The capacitance C
windings of the step-up transformer and the capacitance C of the
generator circuit form a potential divider that determines the
potential of the generator star-point (see Fig. 3.5.11.3a). The
value of the capacitance C is usually too low to reliably hold the
star-point below the pick-up setting of the protection. For this
reason, the generator star-point is grounded via a resistor R
(see Fig. 3.5.11.4)
point remains below the setting of the protection for an E/F on
the HV power system. Correspondingly, the value of the resistor
R
is chosen such that for a given C
E
terminals of the step-up transformer, the offset of the generator
star-point does not reach the pick-up setting of the 95 % E/F
protection.
3 C
12
Star-point
U
3 C
I
a) without grounding resistor
Fig. 3.5.11.3
Generator star-point off-set for an E/F on the HV
side of the step-up transformer
Fig.
3.5.11.2, the relay setting for a zone of
. The scheme detects E/F's on
max
which ensures that the potential of the star-
U
HV
3
E
ABB Switzerland Ltd
between HV and LV
12
and an E/F at the HV
12
3 C
12
R
U
E
I
E
HEST 905 030 FL
b) simplified circuit with
grounding resistor
E
U
HV
3
3-123

Advertisement

Table of Contents
loading

Table of Contents