ABB REG316 4 Series Operating Instructions Manual page 92

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
D. Generator differential function settings - Diff-Gen
Summary of parameters:
Text
Unit
ParSet 4..1
Trip
g-Setting
IN
v-Setting
CurrentInp
AnalogAddr
BlockInp
BinaryAddr
Trip
SignalAddr
Trip-R
SignalAddr
Trip-S
SignalAddr
Trip-T
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the Tripping channel activated by the tripping output
of the function (tripping logic).
g-Setting
Basic setting (sensitivity) g of the operating characteristic.
v-Setting
Pick-up ratio (slope) of the operating characteristic.
CurrentInp
defines the A/D input channels. The first channel (R phase)
of the two groups of three phases must be specified.
BlockInp
Binary address used as blocking input.
F:
- Not blocked
T:
- Blocked
xx:
- all binary inputs (or outputs of a protection
function).
3-54
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
000000
0.10
0.10
0.25
0.25
0
F
ER
(see Section
5.11.).
Max.
Step
0.50
0.05
0.50
0.25