D. Underimpedance function settings - Underimped
Summary of parameters:
Text
Unit
ParSet 4..1
Trip
Delay
s
Z-Setting
UN/IN
NrOfPhases
CurrentInp
AnalogAddr
VoltageInp
AnalogAddr
BlockInp
BinaryAddr
Trip
SignalAddr
Start
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the tripping channel activated by the tripping output of
the function (tripping logic).
Delay
Time between the function picking up and tripping.
Z-Setting
Pick-up impedance setting.
NrOfPhases
defines whether single or three-phase measurement.
CurrentInp
defines the analogue current input channel.
All current inputs may be selected.
In the case of three-phase measurement, the first channel
(R phase) of the group of three selected must be specified.
3-146
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
00.50
0.20
0.250
0.025
001
1
0
0
F
ER
ER
(see Section
5.11.).
Max.
Step
60.00
0.01
2.500
0.001
3
1