Timers; Binary Inputs; Binary Signals - ABB REG316 4 Series Operating Instructions Manual

Numerical generator protection
Table of Contents

Advertisement

REG 316*4 1MRB520049-Uen / Rev. F
3.6.1.1.2.

Timers

EXTIN signals of the time factor type and signals belonging to
the TMSEC group are displayed in this window.
The signals can be connected to the following sources:
· Measured variable constant
Setting range and resolution:
TMSEC signal group:
TIMEFACTOR signal group:
· Protection function binary output (measured variable)
Observe the factors ms (TON), 10 ms (TONS), 1 s (TONL).
· Input from the IBB
Observe the factors ms (TON), 10 ms (TONS), 1 s (TONL).
3.6.1.1.3.

Binary inputs

Binary inputs can be connected to the following sources:
· Always ON ("1")
· Always OFF ("0")
· Binary system inputs
· Protection function binary outputs
· Inputs from the IBB: 768 inputs in 24 groups of 32 signals
each.
3.6.1.1.4.

Binary signals

Binary signals can be connected to the following sinks:
· LED's
· Signalling relays
· Event processor (excluding 'BinExtOut' blocks)
· Protection function binary inputs
· Tripping channels
· Outputs to the IBB: 768 inputs in 24 groups of 32 signals
each.
ABB Switzerland Ltd
0...60.000 s,
for TON
0...50.00 s,
for TONS
0...4000 s,
for TONL
3-297