REG 316*4 1MRB520049-Uen / Rev. F
Characteristic angle
Determining the phase-angle of the current provides an addi-
tional criterion for preserving discrimination compared with non-
directional overcurrent protection. The directional sensitivity is
± 180° in relation to the reference voltage. This is illustrated in the
following diagrams. The angles given apply for connection ac-
cording to the connections in
I
R
j
w
U
R
U
U
TR
RS
U
U
T
S
U
ST
a)
j ' = phase-angle between current and voltage
(positive angle)
a = Characteristic angle
L = Border line between operating and restraint areas
a) Definition of current
and voltage
Fig. 3.5.8.2 Vector diagram for a fault in the forwards direction on
R phase
The function determines the power direction by measuring the
phase-angle of the current in relation to the opposite phase-to-
phase voltage. Which current is compared with which voltage
can be seen from the following table.
Current input
Phase-to-neutral voltage
I
U
, U
R
S
I
U
, U
S
T
I
U
, U
T
R
Section
12.
L
Restraint:
cos ( - ) = neg.
j a
'
b)
b) Operating characteristic
T
R
S
ABB Switzerland Ltd
I
R
a = 45°
j'
U
ST
Operation:
j a
cos ( - ) = pos.
'
L
HEST 005 001 C
Calculated voltage
U
= U
- U
ST
S
T
U
= U
- U
TR
T
R
U
= U
- U
RS
R
S
3-101