ABB REG316 4 Series Operating Instructions Manual page 614

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
Test
Injection of rated value at all c.t. and v.t.
inputs (e.g. using test set Type XS 92b)
Activation/deactivation of all binary in-
puts (opto-couplers)
Energisation of all auxiliary tripping re-
lays (using the test function)
Energisation/de-energisation of all aux-
iliary signalling relays (using the test
function)
A further useful facility is provided by the "Display analogue val-
ues" menu which enables the currents and voltages applied to
the protection to be viewed. It can thus be seen whether the am-
plitude and phase of the currents and voltages are correct. The
Appendix in
Index 12
7-16
REG 316*4 1MRB520049-Uen / Rev. C
Faults disclosed
Hardware defective
Wrong rated current
Wrong rated voltage
Wrong reference value
Hardware defective
Incorrect setting
(not inverted)
Incorrect assignment
Hardware defect
Incorrect assignment
Hardware defect
Incorrect assignment
includes a test report.