REG 316*4 1MRB520049-Uen / Rev. F
3.5.7.

Directional definite time overcurrent protection

(DirCurrentDT)
A. Application
Directional overcurrent function for
· detecting phase faults on ring lines
· detecting phase faults on double-circuit lines with an infeed at
one end
· backup protection for a distance protection scheme.
B. Features
· directionally sensitive three-phase phase fault protection
· insensitive to DC component
· insensitive to harmonics
· voltage memory feature for close faults.
C. Inputs and outputs
I. C.t./v.t. inputs
· current
· voltage
II. Binary inputs
· Blocking
· PLC receive
III. Binary outputs
· start
· start R
· start S
· start T
· forwards measurement
· backwards measurement
· tripping
IV. Measurements
· current amplitude
· active power
· voltage amplitude
of the three phase currents (I
A positive measurement indicates the forwards direction
(I
* U
, I
* U
, I
R
ST
S
TR
Amplitudes of the phase-to-phase voltages
(U
, U
, U
).
ST
TR
RS
, I
, I
)
R
S
T
* U
)
T
RS
ABB Switzerland Ltd
3-85