D. Peak value current function settings - Current-Inst
Summary of parameters:
Text
Unit
ParSet 4..1
Trip
Delay
s
I-Setting
IN
f-min
Hz
MaxMin
NrOfPhases
CurrentInp
CT/VT-Addr 0
BlockInp
BinaryAddr
Trip
SignalAddr
Start
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the tripping channel activated by the tripping output of
the function (matrix).
Delay
Time between the function picking up and tripping.
I-Setting
Pick-up current setting.
Setting restrictions:
not > 1.6 I
when supplied from metering cores
·
N
not < 0.2 I
when supplied from protection cores.
·
N
f-min
defines the minimum frequency for which measurement is
required.
Setting restriction:
not < 40 Hz when supplied from metering cores.
3-66
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
Max.
P1
(Select)
0000000
0
00.01
0.00
60.00
04.00
0.1
20
40
2
50
MAX
(Select)
001
1
3
F
ER
ER
(see Section
5.11.).
Step
0.01
0.1
1
2