D. Inverse time NPS function settings - NPS-Inv
Summary of parameters:
Text
Unit
ParSet 4..1
Trip
k1-Setting
s
k2-Setting
I2/IB
t-min
s
t-max
s
t-Reset
s
CurrentInp
AnalogAddr
IB-Setting
IN
BlockInp
BinaryAddr
Trip
SignalAddr
Start
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the tripping channel activated by the tripping output of
the function (tripping logic).
k1-Setting
Multiplier. Operating characteristic constant.
k2-Setting
Continuously permissible NPS (I
characteristic constant.
Setting restrictions:
not < 0.05 I
/I
N
B
t-min
Definite minimum operating time.
t-max
Maximum delay after being enabled regardless of inverse
characteristic.
3-112
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
10.00
5.00
0.05
0.02
010.0
1.0
1000
500
0030
5
0
1.00
0.50
F
ER
(see Section
/I
2
B
when supplied from protection cores.
Max.
Step
60.00
0.10
0.20
0.01
120.0
0.1
2000
1
2000
1
2.50
0.01
5.11.).
) and operating