9.6.33.
Distance
Basic channel No.: 14
Summary of parameters:
The starter and measurement settings (in columns Min., Max.
and Step) with the unit 'ohms/phase' have to be divided by 10 for
relays with a rated current of 5 A.
Address Access Text
14S4
R
ParSet4..1
14S5
R
TRIP CB R
14S6
R
TRIP CB S
14S7
R
TRIP CB T
14S9
R
X (1)
14S10
R
R (1)
14S11
R
RR (1)
14S12
R
RRE (1)
14S13
R
k0 (1)
14S14
R
k0Ang(1)
14S15
R
Delay(1)
14S16
R
X (2)
14S17
R
R (2)
14S18
R
RR (2)
14S19
R
RRE (2)
14S20
R
k0 (2)
14S21
R
k0Ang(2)
14S22
R
Delay(2)
14S23
R
X (3)
14S24
R
R (3)
14S25
R
RR (3)
14S26
R
RRE (3)
14S27
R
k0 (3)
14S28
R
k0Ang(3)
14S29
R
Delay(3)
24
Unit
Default
<Select>
P1
00000000B
00000000B
00000000B
W/ph
000.00
W/ph
000.00
W/ph
000.00
W/ph
000.00
1
001.00
deg
000.00
s
000.000
W/ph
000.00
W/ph
000.00
W/ph
000.00
W/ph
000.00
1
001.00
deg
000.00
s
000.00
W/ph
000.00
W/ph
000.00
W/ph
000.00
W/ph
000.00
1
001.00
deg
000.00
s
000.00
ABB Switzerland Ltd
Min.
Max.
00000010B 00011110B
-300
300
-300
300
-300
300
-300
300
0
8
-180
90
0
10
-300
300
-300
300
-300
300
-300
300
0
8
-180
90
0
10
-300
300
-300
300
-300
300
-300
300
0
8
-180
90
0
10
Step
0.01
0.01
0.01
0.01
0.01
0.01
0.001
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01