ABB REG316 4 Series Operating Instructions Manual page 696

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
Master mask
· Bit masks.
The bit masks set for every function via the SPA bus apply for
all binary events. No masks are used for analogue events.
· Q events off
As above, but all analogue events are blocked. This is the
default setting and must always be used when the device is
connected to an SCS100.
· Event off
All events are masked (not recorded).
This setting is intended for testing and during commissioning
when it is not wanted that events be transmitted to the control
room.
Receiving
Indicates that valid SPA telegrams have been received.
Initialising
Indicates that the device is being initialised.
The following parameters determine the access rights of the re-
mote HMI and can only be configured on the local HMI
Section
5.12.):
· RemoteMMC
Enables or disables the remote HMI.
· TimeSync
Enables or disables synchronisation by the remote HMI.
· SPAComm
Enables or disables the SPA communication window on the
remote HMI.
· TestFunct.
Enables or disables the test function on the remote HMI.
· Load code
Enables or disables the downloading of a 'setfile' from the re-
mote HMI.
9-8
REG 316*4 1MRB520049-Uen / Rev. E
on / off
on / off
on / off
on / off
on / off
(see