ABB REG316 4 Series Operating Instructions Manual page 178

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
D. Peak value voltage function settings - Voltage-Inst
Summary of parameters:
Text
Unit
ParSet 4..1
Trip
Delay
s
V-Setting
UN
f-min
Hz
MaxMin
NrOfPhases
VoltageInp
CT/VT-Addr
BlockInp
BinaryAddr
Trip
SignalAddr
Start
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the tripping channel activated by the tripping O/P of
the function (matrix).
Delay
Time between the function picking up and tripping.
V-Setting
Pick-up voltage setting.
f-min
defines the minimum frequency for which measurement is
required.
MaxMin
defines operation as overvoltage or undervoltage. Settings:
MAX: overvoltage
·
MIN: undervoltage.
·
NrOfPhases
defines whether single or three-phase measurement.
3-140
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
00.01
0.00
1.40
0.01
40
25
MAX
(Select)
001
1
0
F
ER
ER
(see Section
5.11.).
Max.
Step
60.00
0.01
2.00
0.01
50
1
3
2