Fig. 3.5.1.3 Operating characteristic of the transformer differ-
ential protection for low through-fault currents
This characteristic provides higher sensitivity for the detection of
faults in the protection zone.
Example:
Internal fault and rated current flowing through the transformer:
I
I
1
2
=
=
a
4
1
I
I
N
N
-I 2
I
I
=
I
+
I
=
I 4
-
D
1
2
N
I
=
I
´
I
´
cos
H
1
2
Internal faults will thus be reliably detected when a through-cur-
rent is flowing even at the highest setting for "v".
Increased basic setting g-High
The increased basic setting g-High has been provided as a
means of preventing false tripping under particular operating
conditions. It is activated by an external signal.
3-36
REG 316*4 1MRB520049-Uen / Rev. F
b
I
H
2
I
N
=
0
1 I
2 I
HEST 905 003f C
I
=
I 3
N
N
a
=
I 4
´
I 1
´
1
=
I 2
N
N
HEST 905 003e C
N