D. Rotor ground fault settings - Rotor-EFP
Summary of parameters:
Text
ParSet 4..1
Trip
Alarm-Delay
Trip-Delay
RFrAlarmVal
RFrTripVal
REr
Uir
RFr-Adjust
CouplingCap
VoltageInpUi
VoltageInpUr
AdjRErInp
AdjCoupCInp
BlockInp
Trip
StartTrip
Alarm
StartAlarm
InterruptInt
InterruptExt
REr-Adjust
CoupC-Adjust SignalAddr
Extern-Block
*)
REG 316*4 requires an input transformer unit Type 316GW61 K67 assigned to the following
voltage input channels:
3-252
REG 316*4 1MRB520049-Uen / Rev. F
Unit
Default
P1
00000000
s
0.50
s
0.50
k W
10.0
1.0
k W
k W
1.00
V
50
10.0
k W
µF
4.00
*)
CT/VT-Addr. 0
*)
CT/VT-Addr. 0
BinaryAddr
F
BinaryAddr
F
BinaryAddr
F
SignalAddr
ER
SignalAddr
SignalAddr
ER
SignalAddr
SignalAddr
SignalAddr
SignalAddr
SignalAddr
VoltageInpUi: Channel 8
VoltageInpUr: Channel 7.
Min.
Max.
(Select)
0.20
60.00
0.20
60.00
0.1
25.0
0.1
25.0
0.90
5.00
(Select)
8.000
12.00
2.00
10.00
Step
0.01
0.01
0.1
0.1
0.01
0.01
0.01