ABB REG316 4 Series Operating Instructions Manual page 270

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
2.StarptInp
Binary address used as status input. It determines whether
the second star-point is connected in parallel to the first.
(F ® FALSE, T ® TRUE, binary input or output of a protec-
tion function).
AdjMTRInp
switches the protection function to the MTR determination
mode.
(F ® FALSE, T ® TRUE, binary input or output of a protec-
tion function).
AdjREsInp
switches the protection function to the REs determination
mode.
(F ® FALSE, T ® TRUE, binary input or output of a protec-
tion function).
BlockInp
Binary address used as blocking input.
(F ® FALSE, T ® TRUE, binary input or output of a protec-
tion function).
Trip
Output for signalling tripping.
(signal address)
StartTrip
Output for signalling the pick-up of the tripping stage.
(signal address)
Alarm
Output for signalling an alarm.
(signal address)
StartAlarm
Output for signalling the pick-up of the alarm stage.
(signal address)
InterruptInt
Output for signalling an open-circuit injection circuit.
(signal address)
InterruptExt.
Output for signalling an open-circuit measuring circuit.
(signal address)
3-232
REG 316*4 1MRB520049-Uen / Rev. F