Problems Transferring The New Software - ABB REG316 4 Series Operating Instructions Manual

Numerical generator protection
Table of Contents

Advertisement

REG 316*4 1MRB520049-Uen / Rev. C
ABB Switzerland Ltd
After transfer has been completed, the new program starts
automatically and the time stamp of the *.h26 file is saved in the
equipment.
During the whole of this operation do not make any entries at the
keyboard of the PC, as this interrupts the automatic procedure.
7.5.3.

Problems transferring the new software

Problems and errors can never be excluded when transferring
and saving new software (e.g. supply failure during transfer).
Should something of this kind occur, an attempt can be made to
repeat the transfer by executing the batch file again. If the
equipment responds neither to the call by the batch file nor the
HMI, try to reinitialise the equipment by switching the auxiliary
supply off and back again and then repeat the transfer of the
program file.
Should this also prove unsuccessful, the following procedure
must be executed to delete the contents of the program memory
in the main processor unit:
Devices with the main processor unit 316VC61a have to be
opened and the main processor unit removed from them. Fit the
two jumpers X601 and X602 and reinsert the main processor
unit. Switch on the auxiliary supply and wait for thirty seconds.
Switch off the auxiliary supply and withdraw the main processor
again. The program is now deleted. Remove the two jumpers,
plug the main processor in again, reassemble the equipment and
repeat the program transfer procedure.
Switch of the auxiliary supply to devices equipped with main
processor 316VC61b and then insert the pin supplied into the
socket below the SPA or VDEW6 communication interface.
Switch on the auxiliary supply for about thirty seconds, switch it
off again and withdraw the pin. This procedure deletes the pro-
gram and the new program can be loaded after switching on the
auxiliary supply again.
Should the pin not be available, the same procedure can be
used as described in the previous paragraph for the 316VC61a
with the exception that the jumper marked 'TEST' has to be in-
serted instead of X601 and X602.
7-23

Advertisement

Table of Contents
loading