REG 316*4 1MRB520049-Uen / Rev. F
NrOfPhases
defines whether single or three-phase measurement.
VoltInpLine1
defines the 1st. analogue voltage input channel U
In the case of three-phase measurement, the first channel
(R phase) of the group of three selected must be specified.
VoltInpLine2
defines the 2nd. analogue voltage input channel U
In the case of three-phase measurement, the first channel
(R phase) of the group of three selected must be specified.
BlockInp
Binary address used as blocking input.
F:
- Not blocked
T:
- Blocked
xx:
- all binary inputs (or outputs of a protection
function).
Trip
Output for signalling tripping.
Start
Output for signalling pick-up.
Trip-Line1
Same as Trip, but only if the amplitude of the voltage at input
U
is less than that at input U
1
difference per phase in the three-phase mode).
Trip-Line2
Same as Trip, but only if the amplitude of the voltage at input
U
is less than that at input U
2
difference per phase in the three-phase mode).
ABB Switzerland Ltd
(determination of the voltage
2
(determination of the voltage
1
(line 1).
1
(line 2).
2
3-213