Directional overcurrent definite time protection 67
(DIROCDT)
5.4.1

Mode of operation

Directional overcurrent function:
detecting phase faults on ring lines
detecting phase faults on double-circuit lines with an infeed at one end
backup protection for a distance protection scheme
5.4.2

Features

Directional phase fault protection
Insensitive to DC component
Insensitive to harmonics
Voltage memory feature for close faults
5.4.3

Inputs and outputs

5.4.3.1

CT/VT inputs

Current
Voltage
5.4.3.2

Binary inputs

Blocking
PLC receive
5.4.3.3

Binary outputs

Start
Start L1
Start L2
Start L3
Forwards measurement
Backwards measurement
Tripping
5.4.3.4

Measurements

Current amplitude of the three phase currents (IL1, IL2, IL3)
Active power
A positive measurement indicates the forwards direction (IL1 × UL2L3, IS × UL3L1, IL3 ×
UL1L2)
Voltage amplitude of the phase-to-phase voltages (UL2L3, UL3L1, UL1L2)
Bay protection functions REB500
Technical manual
© Copyright 2019 ABB. All rights reserved
Section 5
Bay protection functions
GUID-65CB2975-ADFB-4D2B-8923-3A0C57A02EB7 v1
GUID-0502CD95-362C-4826-9B26-32533106C57C v1
GUID-B92FE713-87AB-48C5-B7E3-B2C694BEF819 v1
GUID-35EB42DC-C990-4FAD-A2BB-F917C4FD096A v1
GUID-4742C8ED-8E75-406E-8618-E7BF2947A0F1 v1
GUID-67F086A8-8A33-44FD-AC5C-097F44217914 v1
99

Advertisement

Table of Contents
loading

Table of Contents