Phase-Phase And Phase-Neutral Voltage Measurements Vmmxu, Vnmmxu; Voltage And Current Sequence Measurements Vmsqi, Cmsqi; Technical Data - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 13
Monitoring
13.4.8.4
13.4.8.5
13.4.9
380
angle compensation at 5, 30 and 100% of rated current. The compensation below
5% and above 100% is constant and linear in between, see figure 193.
Phase currents (amplitude and angle) are available on the outputs and each
amplitude output has a corresponding supervision level output (ILx_RANG). The
supervision output signal is an integer in the interval 0-4, see section
"Measurement
supervision".
Phase-phase and phase-neutral voltage measurements VMMXU,
VNMMXU
The voltage function must be connected to three-phase voltage input in the
configuration tool to be operable. Voltages are handled in the same way as currents
when it comes to class 0.5 calibrations, see above.
The voltages (phase or phase-phase voltage, amplitude and angle) are available on
the outputs and each amplitude output has a corresponding supervision level output
(ULxy_RANG). The supervision output signal is an integer in the interval 0-4, see
section
"Measurement

Voltage and current sequence measurements VMSQI, CMSQI

The measurement functions must be connected to three-phase current (CMSQI) or
voltage (VMSQI) input in the configuration tool to be operable. No outputs, but
XRANG, are calculated within the measuring block and it is not possible to
calibrate the signals. Input signals are obtained from the pre-processing block and
transferred to corresponding output.
Positive, negative and three times zero sequence quantities are available on the
outputs (voltage and current, amplitude and angle). Each amplitude output has a
corresponding supervision level output (X_RANGE). The output signal is an
integer in the interval 0-4, see section

Technical data

Table 308:
CVMMXN technical data
Function
Voltage
Connected current
Active power, P
Reactive power, Q
Apparent power, S
Table continues on next page
supervision".
"Measurement
Range or value
(0.1-1.5) ×U
r
(0.2-4.0) × I
r
0.1 x U
< U < 1.5 x U
r
0.2 x I
< I < 4.0 x I
r
r
0.1 x U
< U < 1.5 x U
r
0.2 x I
< I < 4.0 x I
r
r
0.1 x U
< U < 1.5 x U
r
0.2 x I
< I < 4.0 x I
r
r
1MRK 502 034-UEN -
supervision".
Accuracy
± 0.5% of U
at U£U
r
± 0.5% of U at U > U
± 0.5% of I
at I £ I
r
± 0.5% of I at I > I
± 1.0% of S
at S ≤ S
r
r
± 1.0% of S at S > S
± 1.0% of S
at S ≤ S
r
r
± 1.0% of S at S > S
± 1.0% of S
at S ≤ S
r
r
± 1.0% of S at S > S
Technical Manual
r
r
r
r
1)
r
r
1)
r
r
r
r