1MRK 505 208-UEN B
11.1.6
11.2
11.2.1
11.2.2
Technical reference manual
Technical data
Table 185:
SMBRREC technical data
Function
Number of autoreclosing shots
Autoreclosing open time:
shot 1 - t1 1Ph
shot 1 - t1 2Ph
shot 1 - t1 3PhHS
shot 1 - t1 3PhDld
shot 2 - t2
shot 3 - t3
shot 4 - t4
shot 5 - t5
Extended autorecloser open time
Autorecloser maximum wait time for sync
Maximum trip pulse duration
Inhibit reset time
Reclaim time
Minimum time CB must be closed before AR
becomes ready for autoreclosing cycle
Circuit breaker closing pulse length
CB check time before unsuccessful
Wait for master release
Wait time after close command before
proceeding to next shot
Apparatus control APC
Introduction
The apparatus control functions are used for control and supervision of circuit
breakers, disconnectors and earthing switches within a bay. Permission to operate
is given after evaluation of conditions from other functions such as interlocking,
synchrocheck, operator place selection and external or internal blockings.
In normal security, the command is processed and the resulting position is not
supervised. However with enhanced security, the command is processed and the
resulting position is supervised.
Error handling
Depending on the error that occurs during the command sequence the error signal
will be set with a value. Table
Range or value
1 - 5
(0.000-60.000) s
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.000-60.000) s
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
186
describes vendor specific cause values in
Section 11
Control
Accuracy
-
± 0.5% ± 10 ms
325