Table 14-10
Response if the converter was not able to completely execute the change request
Data block
Header
Values, parameter 1
Values, parameter 2
...
Values, parameter m
14.4.7.4

Error value 1 for read and change requests

Overview
If the converter receives an erroneous request to read or change parameter values, then the
response from the converter will contain one or two error values. Error value 1 provides
information about the type of faulty request.
Description of function
Table 14-11
Error value 1
Error
Meaning
value 1
00 hex
Illegal parameter number (access to a parameter that does not exist)
01 hex
Parameter value cannot be changed (change request for a parameter value that cannot be changed)
02 hex
Lower or upper value limit exceeded (change request with a value outside the value limits)
03 hex
Incorrect subindex (access to a parameter index that does not exist)
04 hex
No array (access with a subindex to non-indexed parameters)
05 hex
Incorrect data type (change request with a value that does not match the data type of the parameter)
06 hex
Setting not permitted, only resetting (change request with a value not equal to 0 without permission)
07 hex
Descriptive element cannot be changed (change request to a descriptive element that cannot be changed)
09 hex
Description data not available (access to a description that does not exist, parameter value is available)
0B hex
No master control (change request but with no master control)
0F hex
Text array does not exist (although the parameter value is available, the request is made to a text array that does not
exist)
11 hex
Request cannot be executed due to the operating state (access is not possible for temporary reasons that are not
specified)
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
Byte n
Reference (identical to a change request)
01 hex (ID of drive objects, for G120 al‐
ways = 01 hex)
Format
40 hex: Zero (change request for this data block
executed)
44 hex: Error (change request for this data block
not executed)
Only for "Error" - error value 1
Only for "Error" - error value 2
Error value 2 is either zero, or it contains the number of the first index where the error occurred.
...
...
...
14.4 PROFINET communication
Bytes n + 1
82 hex: (Converter was not able to completely
execute the write request)
Number of parameters (identical to a change
request)
Number of error values
00 hex
01 hex or 02 hex
Functions