Fixed Speed Setpoint As Setpoint Source - Siemens Sinamics G110M Operating Instructions Manual

Sinamics series distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

Advanced commissioning
6.14 Setpoints
6.14.6

Fixed speed setpoint as setpoint source

In many applications after switching on the motor, all that is needed is to run the motor at a
constant speed or to switch between different speeds.
Example: After it has been switched on, a conveyor belt only runs with two different
velocities.
Interconnecting a fixed speed setpoint with the main setpoint
Figure 6-39
Table 6- 29
Parameter
p1070 = 1024
Selecting the fixed speed setpoint, either direct or binary
The inverter makes a distinction between two methods when selecting the fixed speed
setpoints:
Directly selecting a fixed speed setpoint
You set 4 different fixed speed setpoints. Up to 16 different setpoints are obtained by adding
one or several of the four fixed speed setpoints.
Figure 6-40
Additional information about direct selection can be found in function diagram 3011 in the
List Manual.
218
Fixed speed setpoint as setpoint source
Setting the fixed speed setpoint as setpoint source
Remark
Main setpoint
Interconnect main setpoint with fixed speed setpoint.
Simplified function diagram when directly selecting the fixed speed setpoints
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH