Run the slotShow command. If the blade is in a FAULTY state, run the slotPowerOff and
Action
slotPowerOn commands to trigger another firmwareDownload. If the blade is stuck in LOADING
state, remove and re-insert the blade to trigger another firmwareDownload. If the problem persists,
contact your switch service provider.
Severity
ERROR
SULB-1018
Message
<timestamp>, [SULB-1018], <sequence-number>, AUDIT, ERROR, <system-name>,
Firmwaredownload timed out in slot <Slot number>.
Probable Cause
Indicates there may be an error caused by the blade initialization issue after the new firmware is
downloaded and the blade is rebooted. The error may also be caused by the internal Ethernet issue
or by the persistent storage failure.
Recommended
Run the slotShow command. If the blade is in FAULTY state, run the slotPowerOff and slotPowerOn
Action
commands to trigger another firmwareDownload. If the blade is stuck in LOADING state, remove
and re-insert the blade to trigger another firmwareDownload. If the problem persists, contact your
switch service provider.
Severity
ERROR
SULB-1020
Message
<timestamp>, [SULB-1020], AUDIT, ERROR, <system-name>, New firmware failed to boot
in slot <Slot number>.
Probable Cause
Indicates the BP blade is still running the old image even though it should reboot with the new
image. This error may indicate that the new image has not been loaded correctly to the specified
blade.
Recommended
Run the slotShow command. If the blade is in a FAULTY state, run the slotPowerOff and
Action
slotPowerOn commands to trigger another firmwareDownload to the blade. If the blade is stuck in
LOADING state, remove and re-insert the blade to trigger another firmwareDownload. If the problem
persists, contact your switch service provider.
Severity
ERROR
SULB-1021
Message
<timestamp>, [SULB-1021],<sequence-number>, AUDIT, WARNING, <system-name>,
Firmware is being downloaded to the blade in slot <Slot number>.
Probable Cause
Indicates the firmware is being loaded to the indicated blade.
Recommended
Run the firmwareDownloadStatus command to monitor the firmwareDownload progress. After it
Action
finishes, run the firmwareShow command to verify the firmware versions.
Severity
WARNING