Message
<timestamp>, [HIL-1104], <sequence-number>,, ERROR, <system-name>, Blower <blower
number> faulted, <nominal voltage> (<measured voltage>) is below threshold.
Probable Cause
Indicates that the fan voltage is below threshold.
Recommended
Run the psShow command to verify the power supply status.
Action
Try to reseat the faulty fan field-replaceable units (FRUs) and power supply FRU to verify that they
are seated properly.
If the problem persists, replace the fan FRU or the power supply FRU as necessary.
Severity
ERROR
HIL-1105
Message
<timestamp>, [HIL-1105], <sequence-number>,, ERROR, <system-name>, Switch error,
<nominal voltage> (<measured voltage>) above threshold.
Probable Cause
Indicates that the switch voltage is above threshold. This message is specific to nonbladed
switches and is not applicable to the Brocade 24000 or 48000.
Recommended
For the Brocade 200E, 3250, 3850, 4012, 4016, 4018, 4020, and 4024, the entire switch must
Action
be replaced because these switches do not have field-replaceable units (FRUs).
For the Brocade 3900, replace the motherboard FRU.
For the Brocade 4100 , 4900, 7500, and AP7600, if the 12 volt level is faulty, replace one or both
power supplies; if any other voltage is faulty, replace the entire switch.
Severity
ERROR
HIL-1106
Message
<timestamp>, [HIL-1106], <sequence-number>,, ERROR, <system-name>, Switch error,
<nominal voltage> (<measured voltage>) below threshold.
Probable Cause
Indicates that the switch voltage is below threshold. This message is specific to nonbladed
switches and is not applicable to the Brocade 24000 or 48000.
Recommended
For the Brocade 200E, 3250, 3850, 4012, 4016, 4018, 4020, and 4024, the entire switch must
Action
be replaced because these switches do not have field-replaceable units (FRUs).
For the Brocade 3900, replace the motherboard FRU.
For the Brocade 4100, 4900, 7500, and AP7600, if the 12 volt level is faulty, replace one or both
power supplies; if any other voltage is faulty, replace the entire switch.
Severity
ERROR