Rs-422A/485 Port - Omron CQM1H-SCB41 Operation Manual

Sysmac cqm1h series serial communications board
Hide thumbs Also See for CQM1H-SCB41:
Table of Contents

Advertisement

Component Names and Functions
!Caution Do not connect the 5-V power supply of pin 6 to any external device other
Applicable Connectors
Recommended Cables
2-1-3

RS-422A/485 Port

Protocol
Host Link
Communica-
Half-duplex
tions method
4-wire, 1:1
OK
4-wire, 1:N
OK
2-wire, 1:1
No
2-wire, 1:N
No
Synchroniza-
Start-stop synchronous (asynchronous)
tion
Baud rate
1,200/2,400/4,800/9,600/ 19,200 bps
Connections
1:N (N: 32 Units max.)
Transmission
500 m max.
distance
(The total combined cable length is 500 m max. T-branch lines must be a maximum of 10 m long.)
Interface
Complies with EIA RS-485
Connector Pin Layout
12
than an NT-AL001-E Link Adapter. Otherwise, the external device and the
Serial Communications Board may be damaged.
The following cables are provided for connection to NT-AL001-E Link Adapt-
ers. We recommend that these cables be used.
NT-AL001-E connecting cables: XW2Z-070T-1 (0.7 m)
Socket: XM2A-0901 (OMRON) or equivalent
Hood: XM2S-0911-E (OMRON, conforms to ESD) or equivalent
One Socket and one Hood are provided for each port.
UL2464 AWG28 5P IFS-RVV-SB (UL-approved, Fujikura Ltd.)
AWG28 5P IFVV-SB (not UL-approved, Fujikura Ltd.)
UL2464-SB (MA) 5P 28AWG (7/0.127) (UL-approved, Hitachi Cable, Ltd.)
CO-MA-VV-SB 5P 28AWG (7/0.127) (not UL-approved, Hitachi Cable, Ltd.)
Cable length: 15 m max.
No-protocol
Protocol macros
OK
OK
OK
OK
No
OK
No
OK
Pin No.
1 (See note 1.)
2 (See note 1.)
3
4
5
6 (See note 1.)
7
8 (See note 1.)
9
Shell (See note 2.)
Note
1. When 2-wire connections are used, use pins 1 and 2, or pins 6 and 8.
2. The shell is connected to the ground terminal (GR) of the Power Supply
Unit inside of the Serial Communications Board. Therefore, the cable
shield can be grounded by grounding the GR of the Power Supply Unit.
XW2Z-200T-1 (2 m)
1:1 Data Links
OK
No
No
No
19,200 bps
1:1
Abbreviation
Signal name
SDA
Send data –
SDB
Send data +
NC
Not used
NC
Not used
NC
Not used
RDA
Receive data –
NC
Not used
RDB
Receive data +
NC
Not used
FG
Shield
Section 2-1
1:N NT Links
1:1 NT Links
OK
OK
OK
No
OK
No
OK
No
38,400 bps
19,200 bps
1:N (N: 8 Units
1:1
max.)
I/O
Output
Output
---
---
---
Input
---
Input
---
---