CompoWay/F Master Protocol
Generalpurpose Broadcast with No Conversion and No Response
(Sequence No. 605)
This sequence broadcasts the specified data beginning with the subaddress and SID. No responses are
received and no conversions are performed on the send data.
Send Data Word Allocation (2nd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR(260))
None. (Specify a dummy value for the operand, such as #0000.)
152
+0
Number of send data words
+1
(Undefined)
+2
(Undefined)
Subaddress
+3
(Undefined)
+4
Number of send bytes
Send data
+5
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Always 0000 Hex
+2
MRC
(2 digits Hex)
+3
Always 00 Hex
+4
Number of send bytes (4 digits
BCD)
+5
Send data
on
+0
+2
+4
+6 etc.
SID
0006 to 0128
---
Subaddress (2
Specify the subaddress of the device
digits Hex)
being communicated with.
SID (1 digit Hex) Set the service ID of the required ser-
vice (e.g., retries).
Number of data bytes from the MCR
until the byte just before the ETX.
0 to 490 decimal
The data specified in hexadecimal here
is not converted and the number of
+1
bytes specified in S+4 is sent.
+3
+5