E5ZE Temperature Controller Read Protocol
Read Output Values (Sequence No. 102)
Reads the output values of the control outputs and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Offset
Contents (data format)
+0
Number of receive data words
(4 digits BCD)
+1
Channel 0
Process value (rightmost 4 digits)
(4 digits BCD)
+2
Channel 0
Process value (leftmost 1 digit)
(1 digit BCD)
+15
Channel 7
Process value (rightmost 4 digits)
(4 digits BCD)
+16
Channel 7
Process value (leftmost 1 digit)
(1 digit BCD)
Number of send data words
+0
+1
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits Hex)
Number of receive data words
+0
+1
Output value
+2
Cooling output value
+3
Output value
+4
Cooling output value
~
+15
Output value
Cooling output value
+16
Offset
Contents (data format)
+0
Number of receive data words
(4 digits BCD)
+1
Channel 0
Output value (4 digits BCD)
+2
Channel 0
Cooling output value (4 digits BCD)
+3
Channel 1
Output value (4 digits BCD)
+4
Channel 1
Cooling output value (4 digits BCD)
+15
Channel 7
Output value (4 digits BCD)
+16
Channel 7
Cooling output value (4 digits BCD)
0017
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
F indicates a negative value.
•
•
•
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
F indicates a negative value.
Unit No.
0002 (fixed)
00 to 0F
Channel 0
Channel 1
~
Channel 7
0017
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
•
•
•
0000 to 1000
0000 to 1000
Appendix E
Data
Data
Data
195