E5ZE Temperature Controller Read Protocol
Read Set Point, Process Value, and Output Value
(Sequence No. 103)
Reads the set points, process values, and output values and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
196
Number of send data words
+0
+1
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits Hex)
+0
Number of receive data words
+1
Set point (rightmost 4 digits)
+2
Set point (leftmost 1 digit)
+3
Process value (rightmost 4 digits)
Process value (leftmost 1 digit)
+4
Output value
+5
~
+36
Set point (rightmost 4 digits)
+37
Set point (leftmost 1 digit)
+38
Process value (rightmost 4 digits)
Process value (leftmost 1 digit)
+39
Output value
+40
Offset
Contents (data format)
+0
Number of receive data words
(4 digits BCD)
+1
Channel 0
Set point (rightmost 4 digits)
(4 digits BCD)
+2
Channel 0
Set point (leftmost 1 digit) (1 digit BCD)
+3
Channel 0
Process value (rightmost 4 digits)
(4 digits BCD)
+4
Channel 0
Process value (leftmost 1 digit)
(1 digit BCD)
+5
Channel 0
Output value (4 digits BCD)
+36
Channel 7
Set point (rightmost 4 digits)
(4 digits BCD)
+37
Channel 7
Set point (leftmost 1 digit) (1 digit BCD)
+38
Channel 7
Process value (rightmost 4 digits)
(4 digits BCD)
+39
Channel 7
Process value (leftmost 1 digit)
(1 digit BCD)
+40
Channel 0
Output value (4 digits BCD)
Unit No.
0002 (fixed)
00 to OF
Channel 0
~
Channel 7
0041
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
0000 to 1000
•
•
•
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
0000 to 1000
Appendix E
Data
Data