V500/V520 Bar Code Reader Protocol
Log Data Output Request (V500) (Sequence No. 356)
This sequence requests output of the log data sent to host.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Note No retries are performed for this sequence.
314
+0
Number of send data words
(Undefined)
+1
Number of units
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Number of units (2 digits BCD)
+0
Number of receive data words
Log data
+1
Log data
+2
~
Log data
+125
+126
Log data
Offset
Contents (data format)
+0
Number of receive data words
(4 digits BCD)
+1 to
Log data (ASCII)
+126
0002 (fixed)
01 to 99
~
0001 to 0127
Log data with the number of desig-
nated data is stored including the sep-
arator GS (1D).
If the log data (including separator)
exceeds 251 bytes, only 251 bytes are
stored.