E5ZE Temperature Controller Write Protocol
Write Set Point (Setting Unit 0.1) (Sequence No. 151)
Writes the set points using a setting unit of 0.1 (5 digits).
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note When the setting unit for the set point is 1 (4 digits), use Write Set Point (Setting Unit 1), Sequence
No.150.
Number of send data words
+0
(Undefined)
+1
Set point (rightmost 4 digits)
+2
+3
Set point (leftmost 1 digit)
Set point (rightmost 4 digits)
+4
Set point (leftmost 1 digit)
+5
~
Set point (rightmost 4 digits)
+16
Set point (leftmost 1 digit)
+17
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits Hex)
+2
Channel 0
Set point (rightmost 4 digits)
(4 digits BCD)
+3
Channel 0
Set point (leftmost 1 digit) (1 digit BCD)
+16
Channel 7
Set point (rightmost 4 digits)
(4 digits BCD)
+17
Channel 7
Set point (rightmost 1 digit)
(1 digit BCD)
Unit No.
Channel 0
Channel 1
~
Channel 7
0018 (fixed)
00 to 0F
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.