Connections In Loopback Test; Rs-232C And Rs-422A/485 Wiring; Recommended Rs-232C Wiring Examples - Omron SYSMAC CS1W-SCB41-V1 Operation Manual

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

RS-232C and RS-422A/485 Wiring

1:N, 2-wire Connections from RS-422A/485 to RS-422A/485 Ports

3-3-12 Connections in Loopback Test

3-4
RS-232C and RS-422A/485 Wiring
3-4-1

Recommended RS-232C Wiring Examples

1,2,3...
114
Serial Communications
Board/Unit
RS-422A/
485 Inter-
face
Communications Mode: 1:N NT Link
Note
1. Serial Communications Board/Unit settings:
Terminating resistance ON, 2-wire.
2. The terminating resistant setting shown above is an example for the
NT631/NT631C. The setting method varies with the PT. Refer to the man-
ual for you PT for details.
Connect the communications ports as shown below.
It is recommended that RS-232C cables be connected as described below
especially when the Serial Communications Board or Unit is used in an envi-
ronment where it is likely to be subject to electrical noise.
1. Always use shielded twisted-pair cables as communications cables.
UL2464 AWG28x5P IFS-RVV-SB (UL product)
AWG28x5P IFVV-SB (non-UL product)
UL2464-SB (MA) 5Px28AWG (7/0.127) (UL product) CO-
MA-VV-SB 5Px28AWG (7/0.127) (non-UL product)
Signal
Pin
Hood
D-sub, 9-pin
connector (male)
RS-232C port
Pin
Signal
SD
RD
RTS
CTS
FG
DTR
DSR
Model
Section 3-4
PT
Signal
RS-422A
-
/485 In
terface
FG
Terminal block
(See note 2.)
Short bar
PT
Signal
RS-422A
/485 In-
terface
FG
Terminal block
RS-422A/485 port
Pin
Signal
Manufacturer
Fujikura Ltd.
Hitachi Cable, Ltd.

Hide quick links:

Advertisement

Table of Contents
loading