Omron CQM1H-SCB41 Operation Manual page 233

Sysmac cqm1h series serial communications board
Hide thumbs Also See for CQM1H-SCB41:
Table of Contents

Advertisement

E5ZE Temperature Controller Write Protocol
Write Alarm Temperature (Setting Unit 0.1) (Sequence No. 157)
Writes the alarm temperatures using a setting unit of 0.1 (5 digits)
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
218
Number of send data words
+0
+1
(Undefined)
Alarm 1 set value (rightmost 4 digits)
+2
Alarm 1 set value (leftmost 1 digit)
+3
Alarm 2 set value (rightmost 4 digits)
+4
Alarm 2 set value (leftmost 1 digit)
+5
~
Alarm 1 set value (rightmost 4 digits)
+30
Alarm 1 set value (leftmost 1 digit)
+31
Alarm 2 set value (rightmost 4 digits)
+32
Alarm 2 set value (leftmost 1 digit)
+33
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits Hex)
+2
Channel 0
Alarm 1 set value (rightmost 4 digits)
(4 digits BCD)
+3
Channel 0
Alarm 1 set value (leftmost 1 digits)
(4 digits BCD)
+4
Channel 0
Alarm 2 set value (rightmost 4 digits)
(4 digits BCD)
+5
Channel 0
Alarm 2 set value (leftmost 1 digits)
(4 digits BCD)
+32
Channel 7
Alarm 2 set value (rightmost 4 digits)
(4 digits BCD)
+33
Channel 7
Alarm 2 set value (leftmost 1 digits)
(4 digits BCD)
Unit No.
Channel 0
~
Channel 7
0034 (fixed)
00 to 0F
0000 to 9999
0000 to 0009
0000 to 9999
0000 to 0009
0000 to 9999
0000 to 0009
Appendix F
Data

Advertisement

Table of Contents
loading

Table of Contents