E5@J Temperature Controller Protocol
Read Parameters 1 (Sequence No. 208)
Reads the set points, alarm values 1, alarm values 2, and heater burnout alarm values for multiple units and
stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
238
Number of send data words
+0
+1
Number of units
+2
(Undefined)
~
+26
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Number of units (4 digits BCD)
+2
1st unit
Unit No. (2 digits BCD)
+3
2nd unit
Unit No. (2 digits BCD)
+26
25th unit
(max.)
Unit No. (2 digits BCD)
Number of receive data words
+0
Set point
+1
Alarm value 1
+2
Alarm value 2
+3
Heater burnout alarm value
+4
~
Set point
+97
Alarm value 1
+98
+99
Alarm value 2
+100
Heater burnout alarm value
Unit No.
~
(max.)
Unit No.
Number of units + 2
0001 to 0025
00 to 31
00 to 31
•
•
•
00 to 31
1st unit
~
25th unit (max.)
Appendix G