Application Procedure - Omron CQM1H-SCB41 Operation Manual

Sysmac cqm1h series serial communications board
Hide thumbs Also See for CQM1H-SCB41:
Table of Contents

Advertisement

Application Procedure

8-2
Application Procedure
1,2,3...
118
6. With some PTs, timeout settings can be changed to eliminate some of the
communications errors. Refer to the operation manual for the PT for de-
tails. This is true in both 1:1 and 1:N mode.
7. If more PTs are required by the system than allowed by the above restric-
tions in 1:N mode, connect the PTs in smaller groups to different ports.
1. Turn OFF the power supply to the PC.
2. Mount the Board.
3. Connections
Connect the external devices using RS-232C or RS-422 cables. The
TERM and WIRE switches on the front panel of the Board must be set if
the Board is connected using the RS-422A/485 port.
The CPU Unit can be connected to a Programming Console, the CX-Pro-
grammer, or the CX-Protocol as required.
4. Turn ON power.
5. Set the PC Setup settings for the Serial Communications Board.
Use a Programming Console, the CX-Programmer, or the CX-Protocol to
set the settings in the PC Setup between DM 6550 and DM 6559.
Note The settings stored in these words are read constantly; the PC does
not need to be restarted or reset when changes are made to the set-
tings. They will be updated automatically as soon as they are
changed.
NT Link Settings for 1:N Mode
The following table shows the settings for connecting more than one PT
when the highest PT unit number is 5.
Port 1
Port 2
DM 6555
DM 6550
DM 6556
DM 6551
DM 6557
DM 6552
DM 6558
DM 6553
DM 6559
DM 6554
Port Settings are always the same for 1:N-mode NT Links. Settings of the
start bits, stop bits, parity, and baud rate are not necessary and will be ig-
nored.
Set the communications mode to a 1:N-mode NT Link (5 Hex).
Up to 8 PTs can be connected in 1:N mode. Set the highest unit number
of the PTs to be connected as the maximum Programmable Terminal unit
number.
NT Link Settings for 1:1 Mode
The following table shows the settings for a 1:1-mode NT Link.
Port 1
Port 2
DM 6555
DM 6550
Bit(s)
Setting
00 to 07
---
Not used.
08 to 11
5 (BCD)
Maximum Programmable Termi-
nal unit number
1 to 7 (BCD)
NT Link in 1:N mode
12 to 15
5 Hex
Communications mode
NT Link in 1:N mode
00 to 15
---
Not used.
00 to 15
00 to 15
00 to 15
Bit(s)
Setting
00 to 11
---
Not used.
12 to 15
4 Hex
Communications mode
NT Link in 1:1 mode
Section 8-2
Function
Function