E5ZE Temperature Controller Read Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Read Alarm Temperatures (Sequence No. 108)
Reads the alarm temperatures and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words
+0
+1
(Undefined)
+2
(Undefined)
+3
(Undefined)
(Undefined)
+4
~
(Undefined)
+15
(Undefined)
+16
Offset
Contents (data format)
+0
Number of receive data words
(4 digits BCD)
+1
Channel 0
Alarm 1 set code (2 digits Hex)
+2
Channel 0
Alarm 2 set code (2 digits Hex)
+15
Channel 7
Alarm 1 set code (2 digits Hex)
+16
Channel 7
Alarm 2 set code (2 digits Hex)
+0
Number of send data words
+1
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits Hex)
+0
Number of receive data words
+1
Alarm 1 set value (rightmost 4 digits)
+2
Alarm 1 set value (leftmost 1 digit)
Alarm 2 set value (rightmost 4 digits)
+3
Alarm 2 set value (leftmost 1 digit)
+4
~
+29
Alarm 1 set value (rightmost 4 digits)
+30
Alarm 1 set value (rightmost 1 digit)
+31
Alarm 2 set value (rightmost 4 digits)
+32
Alarm 2 set value (leftmost 1 digit)
Alarm 1 set code
Channel 0
Alarm 2 set code
Alarm 1 set code
Channel 1
Alarm 2 set code
~
Alarm 1 set code
Channel 7
Alarm 2 set code
0017
00 to 0C
00 to 0C
•
•
•
00 to 0C
00 to 0C
Unit No.
0002 (fixed)
00 to 0F
Channel 0
~
Channel 7
Appendix E
Data
Data
199