V500/V520 Bar Code Reader Protocol
Protocol Configuration
The configuration of the V500/V520 Bar Code Reader Protocol is shown below.
Sequence
Communications
No.
sequence name
350
BCR read start
351
BCR read stop
352
Data read
353
Complete data read
354
BCR function write
(V500)
355
BCR function read
(V500)
356
Log data output request
(V500)
357
Preset data set (V500)
358
BCR connection confir-
mation (V500)
359
Log data clear (V500)
360
Continuous data read
(scan) (V500)
361
Continuous data read
(interrupt) (V500)
362
BCR initialize
363
Continuous data read
(scan) (V520)
364
Continuous data read
(interrupt) (V520)
365
General-purpose com-
mand 1
366
General-purpose com-
mand 2
Note Ladder Interface Settings
YES:
User settings are required for the 2nd and 3rd operands of PMCR.
NO:
Send word allocation:
Receive word allocation: Set the constant 0000 for the 2rd operand (S).
308
Function
Instructs the Reader to start a BCR read.
Instructs the Reader to stop a BCR read.
Data read by the Reader is received and
saved in the receive words.
Instructs the Reader to start a read. After
the data read by the Reader is received and
saved to the receive words, reading is
stopped.
Writes the operation mode and read func-
tions.
Reads the operation mode and read func-
tions.
Requests output of log data sent to host.
Writes preset data.
Confirms if the Reader is correctly set.
Clear log data.
Performs the following operations repeat-
edly: starts reading, receives data read by
the Reader, saves the data to the receive
words by the scan method.
Performs the following operations repeat-
edly: starts reading, receives data read by
the Reader, saves the data to the receive
words by the interrupt method (interrupt
No.100).
Clears the log, confirms BCR connection,
and sets BCRs.
Performs the following operations repeat-
edly: starts reading, receives data read by
the Reader, saves the data to the receive
words by the scan method.
Performing the following operations repeat-
edly: starts reading, receives data read by
the Reader, saves the data to the receive
words by the interrupt method (interrupt
No.100).
Used to send data of a specified data
length, and receive only ACK as the receive
data.
Used to send data of a specified data
length, and receive ACK together with the
return of other receive data. The frame for-
mat of the receive data, however, has to
contain STX and ETX.
Set a dummy word address for the 3rd operand (D).
Appendix J
Ladder interface
Send word
Receive word
allocation
allocation
No
No
No
No
No
Yes
No
Yes
Yes
No
No
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Yes
No
Yes
Yes
No
No
Yes
No
Yes
Yes
No
Yes
Yes

Advertisement