E5ZE Temperature Controller Write Protocol
Cancel Autotuning (Sequence No. 160)
Cancels Autotuning (AT) for all channels.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Setting Unit (Sequence No. 161)
Writes the setting unit.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Input Shift Value (Sequence No. 162)
Writes the input shift values.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
220
Number of send data words
+0
+1
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits Hex)
+0
Number of send data words
+1
(Undefined)
+2
Write code
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits Hex)
+2
Write code (4 digits BCD)
+0
Number of send data words
+1
(Undefined)
+2
Input shift value
+3
Input shift value
+4
Input shift value
+5
Input shift value
+6
Input shift value
+7
Input shift value
+8
Input shift value
+9
Input shift value
Unit No.
0002 (fixed)
00 to 0F
Unit No.
0003 (fixed)
00 to 0F
0000: unit of 1
0001: unit of 0.1
Unit No.
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Appendix F
Data
Data