Troubleshooting
9-2-3

1:N NT Link Mode

Serial commu-
Indicator
nications mode
display
Serial communi-
---
cations mode is
not set to NT
Link.
Serial communi-
The COMM@
cations mode is
indicators do not
set to NT Link.
flash at all.
(Communica-
tions have not
been electri-
cally estab-
lished.)
The SD and
COMM@ indica-
tors are flashing,
but the Serial
Communica-
tions Board can-
not
communicate
with the Pro-
grammable Ter-
minal (PT).
132
Status
I/O memory
information,
etc.
---
Bits 12 to 15
(Serial Commu-
nications Mode)
of DM 6555/
DM 6550 are set
to a value other
than 5 Hex.
---
---
---
---
Cause
Serial communica-
Set bits 12 to 15 (Serial
tions mode is not set
Communications Mode) of
correctly.
DM 6555/ DM 6550 to
5 Hex.
There is a hardware
Conduct a loopback test in
error.
serial communications
mode to check the trans-
mission lines. If an error
occurs during the test,
replace the Serial Commu-
nications Board.
There is a setting
Correct the PT serial port
error for the PT serial
settings.
port.
The I:N NT Link unit
Review the NT Link unit
number of the PT is
number of the PT.
incorrect.
The same 1:N NT
Link unit number has
been set for more
than one PT
The maximum allow-
Review the PC Setup set-
able NT Link unit
tings.
number is incor-
rectly set for the sys-
tem.
Cables are incor-
Review the wiring or switch
rectly connected.
settings.
The RS-422A/485
port setting (2-wire
or 4-wire) is incor-
rect.
Adapters such as the
NT-AL001-E are
incorrectly wired or
set.
A communications
Review the wiring and
error frequently
installation environment.
occurs due to noise,
etc.
There is a PT hard-
Replace the PT.
ware error.
Section 9-2
Remedy