Application Procedure
are shown below. Perform other processing as required, such as setting
switches on the external device(s).
Serial Communications Board
RS-232C
RS-232C
NT-AL001-E
Terminating resistance
ON, 5-V power supply
required
The CPU Unit can be connected to a Programming Console, the CX-Pro-
grammer, or the CX-Protocol as required.
4. Turn ON power.
5. Set the PC Setup settings for the Serial Communications Board.
Use a Programming Console, the CX-Programmer, or the CX-Protocol to
set the settings in the PC Setup between DM 6550 and DM 6559.
Note The settings stored in these words are read constantly; the PC does
not need to be restarted or reset when changes are made to the set-
tings. They will be updated automatically as soon as they are
changed.
The following table shows the standard settings.
Port 1
Port 2
DM 6555
DM 6550
DM 6556
DM 6551
DM 6557
DM 6552
DM 6558
DM 6553
3G2A9-AL001
RS-422A
/485
RS-422A
/485
Bit(s)
Default
setting
00 to 03
0 Hex
Standard port settings
(1 start bit, 7-bit data, even par-
ity, 2 stop bits, 9,600 bps)
04 to 07
0 Hex
CTS control disabled
08 to 11
---
Not used.
12 to 15
0 Hex
Communications mode
0: Host Link
00 to 07
---
Baud rate: invalid
08 to 15
---
Frame format: Invalid
00 to 15
0000 Hex
Transmission delay: 0 ms
00 to 07
00 BCD
Node number 00
08 to 11
---
Not used.
12 to 15
---
Not used.
Section 4-2
Terminating resistance
ON
Function
37