Omron CQM1H-SCB41 Operation Manual page 241

Sysmac cqm1h series serial communications board
Hide thumbs Also See for CQM1H-SCB41:
Table of Contents

Advertisement

E5ZE Temperature Controller Write Protocol
Write HB and HS Alarm Valid Channels (Sequence No. 170)
Writes the valid or invalid channels of HB alarm and HS alarm.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Heater Burnout and SSR Failure Detection Current
(Sequence No. 171)
Writes the currents for detecting heater burnouts and SSR failures.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
226
Number of send data words
+0
(Undefined)
+1
+2
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits Hex)
+2
Write code (2 digits Hex)
Number of send data words
+0
(Undefined)
+1
Heater burnout detection current
+2
SSR failure detection current
+3
Heater burnout detection current
+4
SSR failure detection current
+5
~
Heater burnout detection current
+16
SSR failure detection current
+17
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits Hex)
+2
Channel 0
Heater burnout detection current
(4 digits BCD)
+3
Channel 0
SSR failure detection current
(4 digits BCD)
+4
Channel 1
Heater burnout detection current
(4 digits BCD)
+5
Channel 1
SSR failure detection current
(4 digits BCD)
+16
Channel 7
Heater burnout detection current
(4 digits BCD)
+17
Channel 7
SSR failure detection current
(4 digits BCD)
Unit No.
Write code
0003 (fixed)
00 to 0F
00 to FF
Unit No.
Channel 0
Channel 1
~
Channel 7
0018 (fixed)
00 to 0F
0000 to 0500
0000 to 0500
0000 to 0500
0000 to 0500
0000 to 0500
0000 to 0500
Appendix F
Data
Data

Advertisement

Table of Contents
loading

Table of Contents