E5ZE Temperature Controller Write Protocol
Start Manual Operation (Sequence No. 176)
Starts manual operation based on the output values that were set for all channels of the specified Unit.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Number of send data words
+0
(Undefined)
+1
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits Hex)
Unit No.
0002 (fixed)
00 to 0F