K3T@ Intelligent Signal Processor Protocol
Write Set Value (by Unit Number) (Sequence No. 302)
This sequence writes each set value (HH, H, L, LL).
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Set Value HH (Continuous Units) (Sequence No. 303)
This sequence writes set value HH for continuous units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words
+0
(Undefined)
Number of units
+1
(Undefined)
Relevant unit No.
+2
Operand
+3
Set value
+4
(Undefined)
+5
~
(Undefined)
Relevant unit No.
+122
Operand
+123
Set value
+124
+125
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Number of units
(2 digits BCD)
+2
Relevant unit No.
(2 digits BCD)
+3
Operand
(ASCII 2 characters)
+4 to +5 Set value
(5 digits BCD)
+124 to
Set value
+125
(5 digits BCD)
Number of send data words
+0
+1
(Undefined)
Number of units
+2
Set value
(Undefined)
+3
~
Set value
+64
+65
(Undefined)
Set value
~
Set value
0006 to 0126
01 to 31
00 to 99
4848 ("HH"),4C4C ("LL")
4820 ("H"),4C20 ("L")
00000 to 99999
Negative sign: F (5th digit BCD)
Example 12345
+4
+5
Same as above
Set value
~
Set value
Appendix I
Data
Example 1234
2345
+4
1234
+5
0001
000F
291