Omron CQM1H-SCB41 Operation Manual page 414

Sysmac cqm1h series serial communications board
Hide thumbs Also See for CQM1H-SCB41:
Table of Contents

Advertisement

V600/V620 ID Controller Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Note If L (management of number of write times) is designated by processing designation, management of
number of write times for Data Carrier of EEPROM is performed.
Control (Sequence No. 541)
This sequence performs I/O operations or I/O reads.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Note 1. The V600/620-CA@A does not support this command.
2. This sequence executes the equivalent of the CONTROL command.
Number of receive data words
+0
(Undefined)
+1
Completion code
Offset
Contents (data format)
+0
Number of receive data
words (4 digits BCD)
+1
Completion code
(2 digits Hexadecimal)
+0
Number of send data words
(Undefined)
Unit No.
+1
+2
(Undefined)
OUT1 operation OUT2 operation
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits BCD)
+2
OUT1 operation (1 digit BCD)
OUT2 operation (1 digit BCD)
Number of receive data words
+0
Output status after
+1
Current input status
Offset
Contents (data format)
+0
Number of receive data words
(4 digits BCD)
+1
Current input status
Leftmost 1
Leftmost 4 bits:IN1 operation
byte
Rightmost 4 bits:IN2 operation
Output status after operation
Leftmost 4 bits:OUT1 operation
Rightmost 4 bits:OUT2 operation
0002 (fixed)
(Verification, calculation designation)
00:Normal completion for calculation processing
75: Data in normal condition for verification process-
ing
76: Error Data alarm for verification processing
(If management of number of write times is desig-
nated)
75:Number of write times is under those which is
specified.
76:alarm for number of write times is over those
which is specified.
0003 (fixed)
00 to 07 (CD1D)
0: No operation
1: turned ON
2: turned OFF
0: No operation
1: turned ON
2: turned OFF
operation
0002 (fixed)
1: ON status
0: OFF status
1: ON status
0: OFF status
Appendix M
Data
Data
Data
399

Advertisement

Table of Contents
loading

Table of Contents