Omron CQM1H-SCB41 Operation Manual page 251

Sysmac cqm1h series serial communications board
Hide thumbs Also See for CQM1H-SCB41:
Table of Contents

Advertisement

E5@J Temperature Controller Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Parameters 2 (Sequence No. 206)
Writes the proportional bands, integral times, and derivative times to multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
236
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Number of units (4 digits BCD)
+2
1st unit
Unit No. (2 digits BCD)
+3
1st unit
set point (4 digits BCD)
+4
1st unit
Alarm value 1 (4 digits BCD)
+5
1st unit
Alarm value 2 (4 digits BCD)
+6
1st unit
Heater burnout alarm value 2
(4 digits BCD)
+7
2nd unit
Unit No. (2 digits BCD)
+126
25th unit
(max.)
Heater burnout alarm value 2
(4 digits BCD)
+0
Number of send data words
+1
Number of units
(Undefined)
+2
+3
Proportional band
+4
Integral time
+5
Derivative time
~
+122
(Undefined)
+123
Proportional band
+124
Integral time
Derivative time
+125
Number of units
0001 to 0025
00 to 31
0000 to 9999
0000 to 9999
0000 to 9999
0000 to 9999
00 to 31
0000 to 9999
Unit No.
1st unit
~
Unit No.
31th unit (max.)
Appendix G
Data
5 + 2