E5ZE Temperature Controller Read Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Read Present Set Point (Sequence No. 116)
Reads the present set points during ramp operation and stores the results in the specified word.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
204
+0
Number of receive data words
+1
(Undefined)
+2
Time unit
+3
(Undefined)
+4
Time unit
~
+15
(Undefined)
+16
Time unit
Offset
Contents (data format)
+0
Number of receive data words
(4 digits BCD)
+1
Channel 0
Ramp value (3 digits BCD)
+2
Channel 0
Time unit (one ASCII character)
+15
Channel 7
Ramp value (3 digits BCD)
+16
Channel 7
Time unit (one ASCII character)
Number of send data words
+0
(Undefined)
+1
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits Hex)
Number of receive data words
+0
+1
Present set point (rightmost 4 digits)
+2
Present set point (leftmost 1 digit)
~
+15
Present set point (rightmost 4 digits)
+16
Present set point (leftmost 1 digit)
Ramp value
(Undefined)
Ramp value
(Undefined)
~
Ramp value
(Undefined)
0017
000 to 999
S: Seconds; M: Minutes; H: Hours
000 to 999
S: Seconds; M: Minutes; H: Hours
Unit No.
0002 (fixed)
00 to 0F
Channel 0
~
Channel 7
Appendix E
Channel 0
Channel 1
Channel 7
Data