Omron CQM1H-SCB41 Operation Manual page 258

Sysmac cqm1h series serial communications board
Hide thumbs Also See for CQM1H-SCB41:
Table of Contents

Advertisement

E5@J Temperature Controller Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
General-purpose Write (Sequence No. 216)
Writes the parameter specified by setting a header code.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
General-purpose Read (Sequence No. 217)
Reads the parameter specified by setting a header.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words
+0
(Undefined)
+1
+2
Alarm 1 type
(Undefined)
Offset
Contents (data format)
+0
Number of receive data words
(4 digits BCD)
+1
Status (2 digits Hex)
+2
Alarm 1 type (1 digit Hex)
Alarm 2 type (1 digit Hex)
Input type (1 digit BCD)
+0
Number of send data words
+1
(Undefined)
+2
Header code (ASC)
+3
Data code
(Undefined)
Send data
+4
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits BCD)
+2
Header code (two ASCII characters)
+3
Data code (2 digits BCD)
+4
Write data (4 digits BCD)
Number of send data words
+0
+1
(Undefined)
+2
Header code (ASC)
+3
(Undefined)
Data code
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits BCD)
+2
Header code (two ASCII characters)
+3
Data code (2 digits BCD)
Number of receive data words
+0
Receive data
+1
Status
Alarm 2 type
Input type
0003
00 to 99
0 to 9
0 to 9
0 to 9
Unit No.
0005 (fixed)
00 to 31
Header codes that can be set
MB, WS, W%, WW, WB, WN, WV
01 to 02
0000 to 9999
Unit No.
0004 (fixed)
00 to 31
Header codes that can be set
RS, R%, RW, RB, RN, RV, RO
01 to 02
Appendix G
Data
Data
Data
243

Advertisement

Table of Contents
loading

Table of Contents