E5@J Temperature Controller Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Input Shift Value (Sequence No. 207)
Writes the input shift value.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Number of units (4 digits BCD)
+2
1st unit Unit No. (2 digits BCD)
+3
1st unit
Proportional band (4 digits BCD)
+4
1st unit
Integral time (4 digits BCD)
+5
1st unit
Derivative time (4 digits BCD)
+6
2nd unit
Unit No. (2 digits BCD)
+125
31th unit
(max.)
Derivative time (4 digits BCD)
+0
Number of send data words
(Undefined)
Unit No.
+1
+2
Input shift value
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits BCD)
+2
Input shift value (4 digits BCD)
Number of units
0001 to 0031
00 to 31
0000 to 9999
0000 to 9999
0000 to 9999
00 to 31
•
•
•
0000 to 9999
0003 (fixed)
00 to 31
0000 to 9999
Appendix G
Data
4 + 2
Data
237