Omron CQM1H-SCB41 Operation Manual page 183

Sysmac cqm1h series serial communications board
Hide thumbs Also See for CQM1H-SCB41:
Table of Contents

Advertisement

E5@K Digital Controller Read Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
168
+0
Number of receive data words
+1
Cooling coefficient
+2
Dead band
+3
Manual reset value
+4
Hysteresis (heating)
+5
Hysteresis (cooling)
+6
Control period (heating)
+7
Control period (cooling)
~
+50
Cooling coefficient
+51
Dead band
+52
Manual reset value
+53
Hysteresis (heating)
+54
Hysteresis (cooling)
+55
Control period (heating)
+56
Control period (cooling)
Offset
Contents (data format)
+0
Number of receive data words
(4 digits BCD)
+1
1st unit
Cooling coefficient (4 digits BCD)
+2
1st unit
Dead band (4 digits BCD)
+3
1st unit
Manual reset value
(4 digits BCD)
+4
1st unit
Hysteresis (heating)
(4 digits BCD)
+5
1st unit
Hysteresis (cooling) (4 digits BCD)
+6
1st unit
Control period (heating)
(4 digits BCD)
+7
1st unit
Control period (cooling)
(4 digits BCD)
+56
8th unit
(max.)
Control period (cooling)
(4 digits BCD)
1st unit
~
8th unit (max.)
Number of units
0001 to 9999
A999 to 9999
F indicates a negative value and A indi-
cates –1.
0000 to 1000
0001 to 9999
0001 to 9999
0001 to 0099
0001 to 0099
0001 to 0099
Appendix C
Data
7 + 1

Advertisement

Table of Contents
loading

Table of Contents