Omron CQM1H-SCB41 Operation Manual page 310

Sysmac cqm1h series serial communications board
Hide thumbs Also See for CQM1H-SCB41:
Table of Contents

Advertisement

K3T@ Intelligent Signal Processor Protocol
Write Set Value O2 with Bank (Continuous Units)
(Sequence No. 315)
This sequence writes set value O2 of a bank not in use for continuous units. The word allocation is identical to
that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value O1 with Bank (Continuous Units)
(Sequence No. 316)
This sequence writes set value O1 of a bank not in use for continuous units. The word allocation is identical to
that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Read Set Value (by Unit Number) (Sequence No. 317)
Reads set value HH, H, L, or LL.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR))
Receive data
storage words
+0
Number of send data words
+1
(Undefined)
Number of units
+2
(Undefined)
Relevant unit No.
+3
Operand
~
+64
(Undefined)
Relevant unit No.
+65
Operand
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Number of units
(2 digits BCD)
+2
Relevant unit No.
(2 digits BCD)
+3
Operand
(ASCII 2 characters)
+64 to
Operand
+65
(ASCII 2 characters)
+0
Number of receive data words
+1
(Undefined)
Set value
+2
(Undefined)
+3
~
+94
(Undefined)
Set value
+95
+96
(Undefined)
~
0004 to 0066
01 to 32
00 to 99
4848 ("HH"),4C4C ("LL")4F31 ("01")
4820 ("H"),4C20 ("L")4F35 ("05")
Same as above
End code
Set value
~
End code
Set value
Appendix I
Data
295

Advertisement

Table of Contents
loading

Table of Contents